The low capacity potentiometer tap can then be given a greater capacity by connecting an interface module in series. The 0...10 V signal can be converted into another signal standard, using the AKT, which is also potential-free. It is also possible to digitize directly into 8 or 12 bits by using a Wieland ADW.
![]() [Schematic] |
|
| 10V source | 57.803.8053.0 |
| 10V source with 20 mA source | 57.803.8153.0 |
| Power supply | |
| 10V | 15...30VDC |
| 10V/20mA | 24VDC +/- 20% |
| Power consumption | ca. 10mA |
| Constant voltage | 10.00V (+/- 0.5V) |
| Max. loading capacity (10V unit) | 30 mA |
| Max. loading capacity (10V/20mA unit) | 20 mA |
| Effect of load variation | <= 1%(0...30mA) |
| Constant current (10V/20mA unit) | 20mA(+/- 1 mA) |
| Load | max. 500 ohm |
| Max. error with load variation | <= 1%(0...500 ohm) |