Front plug for S5-S115U Siemens PLC I/O cards

General

This new connection system provides the user with an I/O wiring system which saves both time and money.

There is no costly individual wiring. This is replaced by a precut plug-in flat ribbon cable connection. Numerous interface modules and the appropriate flat-round cables make installation easy.

Application

The front connector provides the connection between the I/O modules of the SIMATIC S 5-115U and the plu-in flat-round cables.

The flat-round cables are connected via a 50-pole ribbon plug connector inaccordance with DIN 41651. This plug connector has long locking levers. Socket connectors with strain relief brackets are recommended for connecting ribbon cables.

Part Number: 87.221.5853.0
Voltage 75V DC/60V AC
Current via quick connect 4.0A
Current via ribbon conn. 2.5A
All other connections 0.5A
Operating temperature 0C...+60C
Storage temperature -40C...+70C


Interface Module

General

Preassembled interface modules are used to connect the sensors and actuators to the I/O plug system. This provides optimum matching to the relevant PLC module.

The connection is extremely simple. The plug-in flat-round cable connects the fron connector and a screw terminal strip connects the sensors and the actuators. This terminal strip is printed with the same numbers as the front connector (1...47). If required, a shield and the protective conductor can be connected at two additional connections (ground). Long and short locking levers are supplied with the ribbon cable plug connector.

Part Number (with LED): 87.221.6053.0
Part Number (w/o LED) 87.221.5953.0
Nominal voltage (with LED) 24 VDC
Nominal voltage (w/o LED) 75 VDC/60 VAC
Nominal current per LED 5 mA
Nominal current,
connections 1, 13, 25, 37
4x2.5A/1x10A
Nominal current,
all other connections
0.5A
Operating temperature 0C...60C
Storage temperature -40C...70C
Digital output modules (with LED) 6ES5 441-7LA11
6ES5 451-7LA11
Digital input modules (with LED) 6ES5 420-7LA11
6ES5 430-7LA11
Digital output modules (w/o LED) 6ES5 441-7LA11
6ES5 451-7LA11
6ES5 457-7LA11
6ES5 458-7LA11
6ES5 482-7LA11


Application

This interface module is suitable for general purpose applications. With the exception of the 6ES5 451-7LA21 module, it is suitable for connection to all digital and analog modules with 46-pole front connectors if the rated maximum nominal voltage and maximum current are not exceeded.


Multi-function module
Part Number 87.221.6353.0
Nominal voltage 75 VDC/60 VAC
Nominal current,
connections 1, 13, 25, 37
2.5 A
Nominal current,
all other connections
0.5 A
Operating temperature 0C...60C
Storage temperature -40C...70C


Front plug for S135-S155U Siemens PLC I/O cards

General

This new connection system provides the user with an I/O wiring system which saves both time and money. There is no costly individual wiring. This is replaced by a precut plug-in flat ribbon cable connection.

Numerous interface modules and the relevant flat-round cables make installation easy.

Application

The front connector provides the connection between the I/O modules of the SIMATIC S5-135U to 155U and the plug-in flat-round cables. The flat-round cables are connected via a 50-pole ribbon plug connector in accordance with DIN 41651. Front connectors 1 and 2 are not connected to the ribbon plug connector. If required, both signals in the front connector can be connected to quick connect terminals X1 and X2. The ribbon cable connector (X1) is fitted with long locking levers as standard. Socket connectors with strain relief brackets are recommended for connecting ribbon cables.


Part Number: 87.222.5853.0
Voltage 75V DC/60V AC
Current via quick connect 6A
Current via ribbon conn. 5A
All other connections 0.5A
Operating temperature 0C...+55C
Storage temperature -40C...+70C


General

Preassembled interface modules are used to connect the sensors and actuators to the I/O plug system. This provided optimum matching to the relevant PLC module.

The connection is extremely simple. The plug-in flat-round cable connects the front connector and a screw terminal strip connects the sensors and actuators. This terminal strip is printed with the same numbers as the front connector (3...42). If required, a shield and the protective conductor can be connected at two additional connections (ground). Front connectors 1 and 2 are not connected to the terminal strip at the interface module. Both signals can be directly connected to the front connector. Long and short locking levers are supplied with the ribbon plug connector.

Part Number (with LED): 87.222.6053.0
Part Number (w/o LED) 87.222.5953.0
Nominal voltage (with LED) 24 VDC
Nominal voltage (w/o LED) 75 VDC/60 VAC
Nominal current per LED 5 mA
Nominal current,
connections 3 and 24 max.
2x5A/1x10A
Nominal current,
all other connections
0.5A
Operating temperature 0C...60C
Storage temperature -40C...70C
Digital output modules 6ES5 441-4UA12
6ES5 451-4UA12
Digital input modules 6ES5 420-4UA12
6ES5 430-4UA12
Digital input/output modules 6ES5 482-4UA12


Application

This interface module is suitable for general purpose applications. It may be used for connection to all digital and analog modules with 42-pole front connectors if the rated maximum nominal current are not exceeded.


Multi-function module
Part Number 87.222.6353.0
Nominal voltage 75 VDC/60 VAC
Nominal current,
connections 3 and 24 max.
5 A
Nominal current,
all other connections
0.5 A
Operating temperature 0C...60C
Storage temperature -40C...70C


Relay output module for S5 - 115U to 155U

Applications

These relay output modules are used to perform a variety of switching functions at PLC output level. The relays are controlled by a digital output module with 32 outputs. Each module (A + B) has 16 plug-in relays. The sequence of the relays corresponds to the same sequence as the PLC outputs. The positive/negative supply to the PLC module is located in each case at the relay module, at terminal strip X2. One fuse with 0.5 A nominal current is installed per byte. Terminal strip X2 has exactly the same terminal marking as the front connector for the S5 - 115 U control system. Each of the jumpers can be plugged in or removed (connected or isolated) as required. Jumpers X3 and X4 may not be removed when connecting control systems S 5 - 135U and S 5 - 155U. In this case +24 V - is connected at terminal 1 or 13 and 25 or 37 and 0 V at terminal 11 or 23 and 35 or 47. Connections 22 and 23 of modules 441-4 and 451-4 are not connected at the relay module.

Part Number: 87.221.6653.0 87.221.6753.0
Input
Voltage 24 VDC +/-10% 24 VDC +/-10%
Current 25 mA 25 mA
Nominal Power 0.6 W 0.6 W
Status Display LED LED
Output
Voltage 250 V AC/DC 250 V AC/DC
Switching Current max. 8 A AC/DC 8 A AC/DC
Continuous Current max. 5 A AC/DC 5 A AC/DC
Voltage/Current min. 12V/100 mA 12V/100 mA
Switching capacity (resistive load) 2000 VA/192 W 2000 VA/192 W
Pickup/dropout delay 8 ms 8 m
Contact material AgCdO AgCdO
Electrical lifetime @ 24VDC/5A 6x105 6x105
Electrical lifetime @ 220VAC/5A 6x105 6x105
Isolation voltage 4kV 4kV
Operating temp. 0C...(see derating curve) 0C...(see derating curve)
Storage temp. -40C...70C -40C...70C
Digital output modules 6ES5 441-7LA11
6ES5 451-7LA11
6ES5 441-4UA12
6ES5 451-4UA12




How to contact us: Wieland may be contacted by calling us at: 1-800-WIELAND
or by email at: sales@wielandinc.com
©1996
Wieland, Inc.
49 International Rd.
Burgaw, NC 28425
comments to: sales@wielandinc.com