![]() [Schematic] |
|||
| Output | |||
| Input | 0...10V | 0...20mA | 4...20mA |
| 0V...+10V | 57.806.0053.0 | 57.806.1553.0 | |
| 0...20mA | 57.806.0253.0 | 57.806.1753.0 | |
| 4...20mA | 57.806.0353.0 | 57.806.1853.0 | |
| Technical Data | |||
| Power Supply | |||
| Supply voltage, reverse polarity protected | 24V DC +/- 20% | ||
| Power consumption w/o output current | ca. 12mA | ||
| Transfer procedure | |||
| Transfer error static at 20C | 0.2 v.E. | ||
| Influence of ambient temperature | 0.015%/K | ||
| Effect of load variation at current output | 0.02%/100ohm | ||
| Limit frequency (sinus 100%) | 20kHz | ||
| Input | |||
| Input res. with standard voltage/current | 1Mohm/49.9ohm | ||
| Voltage drop at 20mA | 1V | ||
| Input protection, dynamic | LC-filter | ||
| Max. perm. input voltage w/ standard voltage/current | 60V/3.5V | ||
| Output | |||
| Internal resistance with standard voltage/current | Ri=100ohm/>5Mohm | ||
| Output protection against interference voltage | Z-diode | ||
| Output load with standard voltage | max. 5mA (RL>= 100Kohm, s. Ri | ||
| Output load for standard current/nominal load | 0...500ohm/100ohm | ||
| Operating temperature | 0C...50C | ||
| Storage temperature | -40C...+85C | ||
When coupling remote components, which often also have several supplies, this signal isolation is imperative in order to prevent ground or earth loops which corrupt the measuring value. With common potential, powerful sources of interference andatmospheric disturbances can cause transient voltage differences so high, that components of the transfer devices can be destroyed. Isolation prevents this to a large degree
The consistent use of the AKT can therefore increase the operational reliability of a system.
![]() |
||||
| Output | ||||
| Input | -10V...+10V | 0...10V | 0...20mA | 4...20mA |
| -10V...+10V | 57.806.1053 | 57.806.2253.0 | 57.806.5653.0 | 57.806.2153.0 |
| 0V...+10V | 57.806.2653.0 | 57.806.1053.0 | 57.806.0653.0 | 57.806.0953.0 |
| 0...20mA | 57.806.2753.0 | 57.806.0753.0 | 57.806.1153.0 | 57.806.1253.0 |
| 4...20mA | 57.806.5553.0 | 57.806.0853.0 | 57.806.1353.0 | 57.806.1153.0 |
| Technical Data | ||||
| Power Supply | ||||
| Supply voltage, reverse polarity protected | 24V DC +/- 20% | |||
| Power consump. 19/24/29V (output signal 20 mA) | ca. 117/88/72 mA | |||
| Transfer procedure | ||||
| Transfer error static at 20C | 0.1% v.E. | |||
| Influence of ambient temperature | 0.02%/K | |||
| Effect of load variation at current output | 0.02%/100ohm | |||
| Limit frequency (sinus 100%) | 20kHz (10kHz +/-10V) | |||
| Dielectric strength of insulation | ||||
| Input/output/supply | 3x2.5kV eff 10 sec. | |||
| Test voltage 1.2/50ms | 4 kV | |||
| All terminals for mounting rail | 2 kV eff. | |||
| Input | ||||
| Input res. with standard voltage/current | 1Mohm/49.9ohm | |||
| Input protection, dynamic | LC-filter | |||
| Max. perm. input voltage w/ standard voltage/current | 60V/3.5V | |||
| Output | ||||
| Internal resistance with standard voltage/current | Ri=100ohm/>5Mohm | |||
| Output protection against interference voltage | Z-diode | |||
| Output load with standard voltage | max. 5mA (RL>= 100Kohm, s. Ri | |||
| Output load for standard current/nominal load | 0...500ohm/100ohm | |||
| Output ripple (2 output filters) | max. 300mVs(40 kHz) | |||
| Operating temperature | 0C...50C | |||
| Storage temperature | -40C...+85C | |||